Description
OMRON CJ1W-TS562 6-Channel RTD (Resistance Temperature Detector) Input Unit. The OMRON CJ1W-TS562 is a 6-channel RTD (Resistance Temperature Detector) input unit for the SYSMAC CJ-series PLC. High Density: Supports 6 independent channels in a single unit, saving space on the PLC rack. Gemini said The OMRON CJ1W-TS562 is a 6-channel RTD (Resistance Temperature Detector) input unit for the SYSMAC CJ-series PLC. It is specifically designed to interface with Pt100 and Pt1000 sensors, making it a critical component for high-accuracy temperature monitoring in industrial processes. +1 Key Features and Capabilities High Density: Supports 6 independent channels in a single unit, saving space on the PLC rack. Dual Sensor Support: Compatible with both Pt100 and Pt1000 platinum resistance thermometers (IEC 60751). High Resolution: Provides a temperature resolution of 0.1°C , with a broad measurement range of -200.0 to +650.0 °C . Signal Integrity: Features automatic leadwire compensation for 3-wire connections, ensuring accuracy even with long cable runs. Configuration: Input types and filter functions (50Hz, 60Hz, or combined suppression) are easily selected via internal DIP switches located behind the terminal block. Technical Specifications Specification Details Number of Inputs 6 channels Measurement Accuracy ± 0.7 % or ± 0.8 °C (whichever is larger) Input Response Time 40 ms to 400 ms (selectable via filters) Current Consumption 250 mA max at 5 VDC (from CJ1 I/O bus) Weight Approx. 150g to 176g Status LEDs RUN (Unit status), ERC (Unit error), 1–6 (Sensor error/disconnection)